NEXPO Products
IED PRODUCTS
넥스포는 Schneider Electric 의 다양한 IED 제품을 통해 전력계통 보호 엔지니어링 솔루션을 제공합니다. Easergy MiCOM과 Vamp는 신뢰성 있는 보호기능과 고급 멀티 기능을 탑재하여 플랜트의 설비들을 안정적으로 보호하고 모니터링함으로써 고객가치 증진에 기여합니다.
VAMP 50/52
IED PRODUCTS
VAMP 50/52
VAMP 50/52
description
VAMP 50 Series
Protection for LV and MV feeders and motors
VAMP 50 series offers a comprehensive selection of modular protection relays for overcurrent, earth fault, voltage, frequency and line differential protection.
저압/고압 전력 시스템을 위한 지능형 보호
VAMP 50 시리즈는 과전류, 접지 결함, 전압, 주파수 및 차동 회선 보호를 위한 포괄적인 모듈형 보호 계전기를 제공합니다.
VAMP 50 Overcurrent and Earth Fault Protection Relay
VAMP 52 Feeder and Motor Protection Relay
VAMP 50: Low and medium voltage feeders in industrial and utility applications with optional arc flash protection and for back-up protection.
VAMP 52: Low and medium voltage feeders in industrial or utility applications with optional arc flash protection. Extensive thermal protection functions make this relay optimal for low and medium-sized asynchronous motors. In feeder configuration mode, autoreclose and directional earth fault are also available.
VAMP 55: Frequency and voltage protection for both utility and industrial applications and also for synchro check applications.
VAMP 59: Line differential protection in medium voltage systems including overhead lines and cables with optional arc flash protection. Intermediate power transformers can be applied within the protected zone.
Specification
VAMP 50/52
Description | Specification | |
---|---|---|
Type (Model Name) | VAMP 50 | VAMP 52 |
Auxiliary Power Supply | 24Vdc 48-230Vac/dc |
|
CT Inputs | 4 | 4 |
VT inputs | 0 | 1 |
Number of Digital input (max) | 7 | 7 |
Number of Digital Output (max) | 6 | 6 |
Analogue input | Option | |
Analogue Output | ||
RTD input | ||
Protection Elements | reverse power and underpower protection (32) Loss of load / under current protection (37) Phase unbalance protection (46) Excessive starting time (48) Thermal overload (49) Ground fault (50N/51N) 3 Phase overcurrent (50/51) Circuit breaker failure (50BF) Over / Under voltage (59/27) Residual over voltage (59N) Intermittent transient intermittent earth-fault protection (67N-IEF) Ground fault directional (67N) Magnetising inrush (68F2) Transformer overexcitation (68F5) Auto-reclose (79) Rate of change of frequency (81R) Current transformer supervision / VT supervision (CTS/VTS) |
|
Communication Protocol | IEC60870-5-101, IEC60870-5-103, DNP3.0, Modbus, SPA-bus, Ethernet IP, Profibus DP, IEC61850 |
Question
Got a question? We'd love to hear from you!